Calculator Results & Worked Examples

Understand the numbers behind battery runtime, appliance energy and off-grid solar sizing. Each example below lists the inputs alongside the calculated result, so you can compare it with your own scenario.

Browse the examples · Explore the calculator library · Read the water-system guide

How to compare a result with your own setup

  1. Open the linked calculator and select the mode that exposes the listed inputs.
  2. Use the stated units, voltage, usable fraction, reserve and conversion factors. Tools can apply reserve differently.
  3. Enter measured appliance demand where available, including accessories and standby use.
  4. Compare the unrounded calculation with the displayed result. A display rounded to one decimal place may differ slightly from the full value.

Results describe the entered energy scenario. Local sunlight, changing loads and battery condition affect real operation. Use the equipment manufacturer’s specifications when selecting components. For formulas and input conventions, see our calculator methodology.

Battery, appliance and solar examples

3000W Inverter Runtime

Inputs: 12V, 100Ah, 90% usable capacity, 90% inverter efficiency and a 3000W load.

972Wh delivered; approximately 19 minutes.

Open this calculator →

Air Conditioner Runtime

Inputs: 5000Wh battery, full health, 90% DoD, 10% additional reserve, 92% inverter efficiency, 8% other loss, 750W at 60% duty plus 120W.

3427.92Wh delivered; 570W average load; approximately 6.01 hours.

Open this calculator →

100Ah TV Runtime

Inputs: 12V 100Ah, 90% usable fraction, 90% efficiency, 60W TV, no reserve or other loads.

972Wh delivered; 16.2 hours; four complete four-hour sessions.

Open this calculator →

Refrigerator Runtime

Inputs: 1000Wh, full health, 90% DoD, zero reserve, 90% efficiency, 10% other loss, 50W measured average at 100% duty.

14.58 hours, displayed as 14.6 hours.

Open this calculator →

Battery Discharge

Inputs: 2000Wh, 50% starting charge, full health, 80% DoD, 90% inverter efficiency and 200W continuously; zero standby; 72°F.

600Wh above reserve before inverter loss; 2.7 hours.

Open this calculator →

Off-Grid System Size

Inputs: 5kWh/day, 2.5 peak sun hours, 80% solar delivery, 25% array margin and 400W panels.

3.125kW minimum array; eight panels totaling 3.2kW.

Open this calculator →